ARCHITECTURAL

 

GUIDE SPECIFICATION

 

FOR

 

RAECO SLU

 

SELF LEVELING UNDERLAYMENT


                                                               (Change to meet requirements) SECTION 03550-1

                                                                          CEMENTITIOUS FLOOR UNDERLAYMENT

 

 

 

PART 1  GENERAL

 

1.01      SECTION INCLUDES

 

            A. Work includes but not limited to the following:

                        1. Polymer modified cementitious self leveling underlayment.

 

1.02      RELATED SECTIONS

 

            A. Coordinate related work specified in other areas of the Project Manual, including but

                  not  limited to the following:

 

            Section 03300 - Cast-In-Place Concrete

            Section 09650 - Resilient Tile Flooring

            Section 09680 - Carpet

 

1.03      REFERENCES

 

            A. Comply with the requirements of Section 01091 and as listed herein. See Section

                 01091 for listed association, council, institute, society, and the like organization for its

                 full name and address.

 

            ASTM C-109                  Test Method for Compressive Strength of Hydraulic Cement

                                                Mortars. (Using 2 inch or 50 mm Cube Specimens)

            ASTM C-190                  Test Method for Tensile Strength of Hydraulic Cement Mortars.

            ASTM C-256                  Test Method for Flexural Strength of Hydraulic Cement Mortars.

 

1.04      SYSTEM DESCRIPTION

 

A.      Portland Cement-based, self leveling polymer modified underlayment to bring

      concrete slab substrates into tolerance and where unsuitable, to receive new floor

      finishes.

 

1.05      PERFORMANCE REQUIREMENTS

 

            A. Resistant to indentation, tightly bonding, non-injurious adhesives and floor finishes.

 

1.06      SUBMITTALS

           

            A. Submittals in accordance with Sections 01300 and the following:

                        1. Product Data: Provide completely definitive brochures including

                              specifications, current product literature and other data to prove compliance

                              with specified requirements.

                        2. Manufacturer’s certification that product is cement based having a cement

                            binder content which is a minimum of 80% of total binder as per ASTM C-114.

                        3. Manufacturer’s certification that product specified is suitable for intended use

                              when installed per manufacturer’s literature and installation instructions.

 

1.07      QUALITY ASSURANCE

 

            A. Applicator Qualifications: Applicator of concrete floor resurfacing shall be approved by

                 manufacturer.

 

            B. Regulatory Requirements: See referenced Codes, Ordinances Section 01060

 

 

                                                                                                                       SECTION 03550-2

                                                                           CEMENTITIOUS FLOOR UNDERLAYMENT

 

 

 

            C. Test Areas: At an area on-site, where approved by Engineer, provide a test

                                    installation as follows:

                        1. Size of area shall be 4’x 4’.

                        2. Test area shall be installed using procedures and under conditions which

                              will reflect actual jobsite conditions.

                        3. Test shall be placed and evaluated for a period of 4 days prior to approval

                              by the Engineer.

                        4. Approval shall deem the test area as the standard by which the remainder of

                             the project shall be compared for the acceptance or rejection.

 

1.08      DELIVERY, STORAGE AND HANDLING

 

            A. In accordance with provisions of Section 01600 and the following: Materials shall be

                 delivered in its original unopened container and protected from contamination,

                 damage or deterioration as per manufacturer’s instructions. All damaged products

                 shall be removed from project and discarded as per local requirements.

 

1.09      PROJECT SITE CONDITIONS

 

            A. Environmental Conditions:

                        1. Maintain enclosed building at minimum of 50 degrees F. before, during and

                             after installation. Provide continuous ventilation and adequate heat to remove

                             moisture until product has adequately cured.

 

1.10      SCHEDULING / SEQUENCING

 

            A. Coordinate with Engineer’s approved Progress Schedule, Section 01310

 

PART 2  PRODUCTS

 

2.01      MANUFACTURER

 

            A. Raeco, Inc.  Seattle, Washington  Tel. (206) 763-1335  Fax (206) 768-0175 is

                 specified for type, material and quantity required.

 

2.02      MATERIALS

 

            A. Raeco SLU, Self Leveling Underlayment in pre-blended sacks.

                       

            B. Raeco-Bond Primer or Raeco R-2000, Bonding Agent.

 

            C. Clean Potable Water

 

            D. Appropriate Aggregate for thickness’ exceeding ½”. Refer to Product Data Sheet

                 for type and size.

           

 

 

 

 

 

 

 

 

 

 

 

                                                                                                               SECTION 03550-3

                                                                        CEMENTITIOUS FLOOR UNDERLAYMENT

           

 

           

            E. Technical Data:

1.       Self leveling polymer modified concrete underlayment that contains no

gypsum, chlorides, ferrous metals or corrosive agents.

                        2. Compressive Strength, 4650 psi @ 28 days, ASTM C-1439

                            Tensile Strength, 520 psi @ 28 days, ASTM C-190

                            Flexural Strength, 1035 psi @ 28 days, ASTM C-256

                            Shear Bond Strength, 500 psi @ 28 days

                            Flammability, ASTM E84

                                    a. Flame Spread            0

                                    b. Fuel Contribution        0

                                    c. Smoke Development   0

                        3. Flow Time:     20 min. @ 70° F.

                            Initial Set:      45 min. @ 70° F.

                            Final Set:      2-3 hrs. @ 70° F.

                        4. Coverage:  50 sq.ft. per sack @ 1/8”

 

2.03      MIXING PROPORTIONS

 

            A. Mix proportions and methods shall be in accordance with product manufacturer

                recommendations.

 

PART 3  EXECUTION

 

3.01      EXAMINATION

 

            A. Verify installation conditions as satisfactory to receive work of this Section. Do not

                 install until unsatisfactory conditions are corrected. Beginning work will constitute your

                 acceptance of conditions as satisfactory.

 

3.02      PREPARATION

 

            A. Condition and Cleaning of Subfloor: Subfloor shall be structurally sound, shot blast,

                 and contaminant free.

 

            B. Cracks in subfloor shall be repaired prior to installation of the underlayment to prevent

                telegraphing through the underlayment.

 

            C. Expansion Joints: Allow joints to continue through the concrete resurfacing material

                 at same width.

 

3.03      APPLICATION

 

            A. Primer: Prime subfloor with specified compound. Priming instruction may vary

                              according to type of substrate, multiple coats may be necessary.

 

            B. Mix and apply in accordance with manufacturer’s written directions.

                        1. Thickness: As required to meet construction conditions. Pour or pump

                                              in place to meet tolerances setforth.

                        2. Drying: Provide continuous ventilation and adequate heating to removing

                                        moisture from the area until dry. Test for dryness in accordance with

                                       manufacturer’s directions.

                       

 

 

 

 

                                                                                                               SECTION 03550-4

                                                                        CEMENTITIOUS FLOOR UNDERLAYMENT

 

 

 

3.04      TOLERANCES

 

            A. Finished surface tolerances shall be 1/8” using a 10’ straight edge, measuring in

                any direction.

 

3.05      PROTECTION

 

            A. Protect from heavy loads during construction, place temporary cover to area by

                 means to protect from contamination and damage.

 

 

 

 

END OF SECTION